Description
Product Overview
The Reliance Electric 0-57400-A is intended for collecting discrete control signals in legacy AutoMax installations. Its 16 input points allow a controller to monitor external states such as auxiliary contacts, interlocks, limit switches, and other control signals compatible with the module’s electrical input requirements. Actual application suitability depends on the field-device voltage, wiring arrangement, and controller configuration.
The module is specified for nominal 115 V AC/DC input signals. Its grouped input architecture is important during maintenance: published information for the 0-57400 family describes four isolated commons with four input points per common. Engineers should confirm the terminal assignments, isolation details, and AC/DC operating limits against manual J-3625 before reconnecting field wiring. Do not assume that a signal is compatible solely because its nominal voltage matches.
This is a legacy AutoMax component, and current replacement planning should account for the condition of available stock and the difficulty of reproducing the original control configuration. Before ordering, match the complete 0-57400-A part number and inspect the module’s terminal connections and circuit-board condition. A supplier’s description of the broader 0-57400 family is useful for identification, but it does not replace verification of the exact suffix and revision.
Product Introduction
The 0-57400-A provides discrete AC/DC input acquisition for Reliance Electric AutoMax rack-based control systems. It is intended to transfer the status of external electrical signals into the control system so that application logic can respond to equipment states and interlocks.
For replacement work, prioritize exact model matching, verification of the 115 V AC/DC field circuit, and review of the original wiring documentation. The related 0-57400 and 0-57400-1 designations should not automatically be treated as interchangeable with the -A variant without checking the applicable hardware documentation.
Key Technical Specifications
| Specification | Details |
|---|---|
| Manufacturer | Reliance Electric |
| Model | 0-57400-A |
| Product type | Digital AC/DC input module |
| System family | AutoMax |
| Number of inputs | 16 points |
| Nominal input voltage | 115 V AC/DC |
| Input frequency | 50/60 Hz listed for the related 0-57400 family; confirm exact revision |
| Input grouping | Four isolated commons, four points per common, per family documentation |
| Isolation | Published family information reports 2,500 V isolation between logic and common; verify the exact module manual |
| Maximum power dissipation | 46 W reported for the broader 0-57400 family; confirm for the -A variant |
| Mounting | AutoMax rack |
| Reference manual | J-3625 |
| Communication interface | Rack backplane; detailed interface specifications not independently verified |
| Operating temperature | Not independently verified |
| Protection rating | Not independently verified |
| Lifecycle status | Listed as discontinued |
| Product condition | Confirm actual condition with supplier |
Specification references: published 0-57400 family information and listings for the exact 0-57400-A model. Family-level figures should be confirmed against manual J-3625 before engineering use.

0-57400-A
Related Products
| Model | Description |
|---|---|
| 0-57400 | Related 16-point, 115 V AC/DC input module |
| 0-57400-1 | Related 115 V input-module variant |
| 0-57400-B | 16-point 115 V output module; different function |
| 0-57402-C | AutoMax 16-channel, 115 V low-output module |
| 0-57404-1 | AutoMax communication module variant |
These parts belong to the broader Reliance Electric AutoMax range. Similar numbering does not establish interchangeability, particularly between input and output modules. Confirm the required I/O function, electrical characteristics, and hardware revision before selecting a substitute.
Frequently Asked Questions
Q1: What is the Reliance Electric 0-57400-A used for?
It reads discrete 115 V AC/DC control signals into an AutoMax control system. Typical uses include equipment status monitoring and control interlocks where the input electrical requirements match the field circuit.
Q2: How many input points does it have?
The 0-57400-A is listed as a 16-point input module.
Q3: Can it accept both AC and DC signals?
Published descriptions identify it as a 115 V AC/DC input module. Verify the exact permitted voltage ranges and wiring instructions in manual J-3625 before connecting field devices.
Q4: Is the 0-57400-A the same as the 0-57400-B?
No. Listings identify the 0-57400-A as an input module and the 0-57400-B as an output module. They perform different functions and should not be substituted for one another.
Q5: Is the 0-57400-A still manufactured?
It is listed as discontinued. Availability may depend on existing inventory, refurbished units, or repair options, so verify the actual condition and test coverage of any offered unit.
Q6: Can this module be replaced while the AutoMax system is running?
Do not assume online replacement is supported. Isolate the relevant electrical circuits and follow the approved AutoMax maintenance procedure before removing or installing the module. Consider the impact on control logic and connected equipment before taking the system offline.
Q7: What should procurement verify before ordering?
Confirm the complete part number 0-57400-A, 16-point input function, 115 V AC/DC rating, module revision, terminal condition, and compatibility with the installed AutoMax rack. For used or refurbished stock, request documented functional test results and clarify whether the testing covers all input channels.