Description
Product Introduction
Electrical power-monitoring faults can make it difficult to distinguish a real load problem from a measurement or communications issue. The GE Fanuc IC660EPM100J is an electronics assembly for the Genius I/O PowerTRAC block, used to acquire voltage and current measurements and calculate electrical operating values for industrial power systems.
Installed with the compatible IC660BPM100 PowerTRAC terminal base, the IC660EPM100J supports monitoring of active and reactive power, power factor, energy, and system frequency. When replacing an existing assembly, verify the input supply, revision, firmware behavior, and voltage/current transformer configuration before returning the equipment to service.
Key Technical Specifications
| Parameter | Specification |
|---|---|
| Product model | IC660EPM100J |
| Manufacturer | GE Fanuc / GE Intelligent Platforms |
| Product family | Genius I/O |
| Product type | PowerTRAC electronics assembly |
| Compatible complete block | IC660BPM100 |
| Nominal AC input | 115/230 VAC |
| AC input range | 90–265 VAC |
| AC frequency | 47–63 Hz |
| Nominal DC input | 125 VDC |
| DC input range | 100–150 VDC |
| Maximum DC input power | 35 VA |
| Voltage measurements | Phase-to-phase and phase-to-neutral, as supported by system wiring |
| Current measurements | Individual phases and neutral |
| Calculated values | Active power, reactive power, power factor, energy, and frequency |
| Update rate | Approximately two updates per second for calculated values and status data |
| Network | Genius I/O bus |
| Local diagnostics | Unit OK and I/O enabled indicators are documented for the PowerTRAC block |
| Installation | Fits the compatible PowerTRAC terminal base |
| Operating temperature | 0°C to +60°C |
| Relative humidity | 5–95%, non-condensing |
| Hot insertion/removal | Not supported |
| Lifecycle | Legacy/discontinued product family |
Specifications are based on the IC660EPM100 documentation and PowerTRAC product references. Confirm the applicable revision manual for the exact IC660EPM100J assembly before wiring or commissioning.

IC660EPM100J
Application Scenarios and Pain Points
In industrial power monitoring, incorrect transformer ratios or loss of bus communications can produce misleading readings. The PowerTRAC assembly helps collect and calculate electrical measurements for monitoring and troubleshooting.
- Plant power monitoring: Tracks voltage, current, active power, reactive power, and power factor.
- Energy measurement: Supplies calculated energy data for electrical usage monitoring.
- Motor and process-load analysis: Helps maintenance teams assess electrical load behavior using configured voltage and current transformer inputs.
- Legacy Genius I/O maintenance: Supports repair of an existing PowerTRAC block without necessarily dismantling the original field termination.
Field note: The PowerTRAC documentation identifies important revision-dependent behavior. For the documented later version, outputs default to zero if communication with the bus controller is interrupted, whereas earlier versions may hold their last state. Confirm the installed revision and application behavior before changing the electronics assembly.
Related Products
- IC660BPM100 — Complete PowerTRAC block that uses the EPM100 electronics assembly.
- IC660BPM100C — Related PowerTRAC block version; verify revision and firmware compatibility.
- IC660HHM501 — Genius I/O Hand-held Monitor family used for configuration and diagnostics, subject to firmware-version requirements.
- IC660CBB902 — Genius bus controller used in Series Six configurations.
- IC697BEM731 — Genius bus controller for Series 90-70 systems.
- IC693CMM301 — Genius communications module for Series 90-30 systems.
- IC660ELB905 — Genius network interface module.
These products belong to the wider Genius I/O ecosystem, but controller compatibility depends on the host PLC, bus configuration, and Hand-held Monitor or firmware version. They are not direct substitutes for the IC660EPM100J.
Engineer’s Guide: Replacement Checks
1. Confirm the assembly and terminal base.
Warning: IC660EPM100J is the electronics assembly, not the complete IC660BPM100 PowerTRAC block. Confirm whether the replacement includes only the electronics or the complete block.
2. Verify the power measurement configuration.
Check the AC or DC supply arrangement, voltage transformer ratio, current transformer ratio, phase configuration, and power-sign convention. Incorrect transformer settings can produce inaccurate power and energy readings.
3. Plan a controlled shutdown.
Hot insertion and removal are not supported. Isolate the equipment using the approved procedure, verify the supply is safe, install the assembly, and then check diagnostics and communications before relying on the reported values.
For a surplus or refurbished unit, request a clear nameplate photograph, revision details, functional-test evidence, confirmation of the included hardware, and written warranty and dispatch terms.
Frequently Asked Questions
Q1. What is the GE Fanuc used for?
It is the electronics assembly for a Genius I/O PowerTRAC block. It measures electrical inputs and calculates values such as power, power factor, energy, and frequency.
Q2. Is a standalone power supply?
No. It is a PowerTRAC electronics assembly with measurement and processing circuitry. It fits the compatible PowerTRAC terminal base and is not simply a general-purpose 24 VDC power supply.
Q3. Which complete block is associated with ?
The documented associated block is IC660BPM100. Verify the exact block revision and configuration before ordering replacement electronics.
Q4. What input voltage does accept?
The IC660EPM100 documentation lists 90–265 VAC at 47–63 Hz or 100–150 VDC, with 125 VDC nominal. Confirm the applicable revision documentation and cabinet supply before connection.
Q5. Can I replace an earlier IC660EPM100 revision with revision J?
Do not assume a direct replacement based only on the shared base model. Check the installed block, firmware, configuration, transformer ratios, and documented revision-specific behavior. Some revisions differ in how they handle communications loss.
Q6. Does the module measure three-phase power?
The PowerTRAC documentation describes phase-to-phase and phase-to-neutral voltage measurement, phase-current measurement, neutral current, and calculated power values. Confirm the required transformer inputs and wiring for the plant’s single-phase or three-phase arrangement.
Q7. What should I verify when buying a used ?
Confirm the complete model and revision, compatibility with the installed IC660BPM100 block, operating condition, test results, warranty coverage, and dispatch lead time. Ask whether the unit has been tested for measurement accuracy and Genius bus communications.