Eaton XV-152-D6-10TVRC-10 | CANopen PLC Touchscreen

  • Model: XV-152-D6-10TVRC-10
  • Manufacturer: Eaton
  • Series: XV-150 / XV-152 operator panels
  • Catalog Number: 150611
  • Core Function: Operator visualization and programmable control for industrial machinery.
  • Product Type: Touchscreen HMI with integrated PLC functionality.
  • Display: 10.4-inch color TFT, VGA resolution (640 × 480), resistive touch.
  • Communications: Ethernet, RS232, RS485, CANopen/easyNet, USB host, and USB device.
  • Power Supply: Nominal 24 VDC.
  • Processor: 32-bit RISC, 400 MHz.
Category: SKU: Eaton XV-152-D6-10TVRC-10

Description

Product Overview

The Eaton XV-152-D6-10TVRC-10 is an industrial human-machine interface (HMI) panel with integrated programmable controller functionality, designed for operator monitoring and machine control. It belongs to Eaton’s XV-150 family and features a 10.4-inch color TFT display with VGA resolution of 640 × 480 pixels and a resistive touchscreen. Its metal housing and panel-mount design suit industrial equipment where operators need direct access to machine status, process values, alarms, and control commands. The unit combines visualization and PLC functionality in one device, reducing the need for separate operator-interface and control hardware in supported applications.

The Eaton XV-152-D6-10TVRC-10 provides Ethernet 10/100 Mbps, RS232, RS485, CANopen/easyNet, USB host, USB device, and an SD card slot. Its 32-bit RISC processor operates at 400 MHz, with 64 MB DRAM, approximately 64 MB NAND flash, 125 KB retentive NVRAM, and 2 MB NOR flash. The panel runs Windows CE 5.0 and supports engineering environments including Galileo and XSOFT-CoDeSys, subject to the installed software and project requirements. It uses a nominal 24 VDC supply and has a documented front protection rating of IP65, with IP20 at the rear.

For maintenance teams, the Eaton XV-152-D6-10TVRC-10 is relevant to legacy machinery where existing HMI screens, PLC logic, and communications must be preserved. Eaton lists the model as discontinued, so replacement planning should include a backup of the application, confirmation of programming-software compatibility, and verification of connected devices and network settings. Before installation, check the exact catalog number, mounting dimensions, power supply, and interface wiring. A newer HMI may offer similar display functions but still require project conversion, driver changes, or PLC communication adjustments.

 

Product Introduction

Replacing an established HMI can involve more than matching screen dimensions. The Eaton XV-152-D6-10TVRC-10 combines a 10.4-inch resistive touchscreen, integrated PLC functionality, and multiple industrial communication interfaces in a single panel. Its VGA display provides a 640 × 480-pixel operator workspace for supported applications.

For legacy equipment, verify the original visualization project, CoDeSys or Galileo software requirements, and communication settings before choosing a replacement. These checks help preserve operator workflows and reduce avoidable commissioning changes.

 

Key Technical Specifications

Parameter Specification
Manufacturer Eaton
Model XV-152-D6-10TVRC-10
Catalog Number 150611
Product Family XV-150 / XV-152
Product Type HMI with integrated PLC functionality
Display Technology Color TFT
Display Size 10.4 inches
Resolution 640 × 480 pixels (VGA)
Touch Technology Four-wire resistive touchscreen
Processor 32-bit RISC, 400 MHz
DRAM 64 MB
NAND Flash Approximately 64 MB
Retentive NVRAM 125 KB
NOR Flash 2 MB
Operating System Windows CE 5.0
Visualization Software Galileo; EPAM; supported project environments vary
PLC Programming XSOFT-CoDeSys 2 / 3, subject to project compatibility
Ethernet 10/100 Mbps
Serial Interfaces 1 × RS232; 1 × RS485
Fieldbus CANopen/easyNet
USB 1 × USB host 2.0; 1 × USB device
External Storage 1 × SD card slot
Nominal Supply Voltage 24 VDC
Permissible Operating Voltage 19.2–30.0 VDC effective
Power Consumption Up to 12 W listed; verify configuration
Dimensions Approximately 345 × 260 × 54 mm (W × H × D)
Protection Rating IP65 front; IP20 rear
Cooling Fanless, natural convection
Operating Temperature 0°C to +50°C
Product Status Discontinued

Specifications are based on Eaton’s product page and XV-152 technical documentation. Confirm the exact revision and installed software before commissioning or replacing an existing unit.

XV-152-D6-10TVRC-10

Related Products

The following products are related XV-152 variants or accessories. Display size, communication interfaces, and application compatibility must be checked before substitution.

  • XV-152-D6-84TVRC-10 — 8.4-inch touchscreen variant with CAN, RS485, and RS232 connectivity. Verify project resolution and mounting dimensions.
  • XV-152-D0-10TVR-10 — 10.4-inch XV-152 variant with RS232 connectivity; does not have the same documented CAN interface configuration.
  • XV-152-D4-10TVR-10 — 10.4-inch version with RS485 and RS232 interfaces; check the interface set against the installed application.
  • XV-152-D8-10TVR-10 — 10.4-inch XV-152 variant with PROFIBUS and serial interfaces. Suitable only where the communication architecture matches.
  • XV-152-E6-10TVR-10 — Related XV-152 version with CAN, RS485, and SmartWire-DT master functionality. Confirm hardware and project compatibility.
  • XV-152-E8-10TVR-10 — Related version offering PROFIBUS, RS485, and SmartWire-DT master connectivity.
  • XV-102 series panels — Related Eaton operator-panel family; verify the specific model’s display, processor, software, and interface support before considering a replacement.
  • SD memory card for XV-152 — Optional external storage for supported applications and data; verify the card specification and project requirements.

 

Frequently Asked Questions

1. What is the Eaton XV-152-D6-10TVRC-10 used for?

It is an industrial touchscreen HMI with integrated PLC functionality. It supports operator visualization and control tasks on compatible machinery, with Ethernet, serial, USB, and CANopen/easyNet connectivity.

2. Does this HMI support CANopen communication?

Yes. The D6 version is documented with CAN communication, identified as CANopen/easyNet in the technical data. Confirm the required protocol, device configuration, and network settings for the actual application.

3. Can I replace it with another 10.4-inch HMI?

Not solely on the basis of screen size. Check the display resolution, panel cutout, communication interfaces, PLC functionality, programming environment, and project conversion requirements. A different HMI may require software changes even if it fits the same panel.

4. Does the XV-152-D6-10TVRC-10 support CoDeSys?

Eaton documentation identifies XSOFT-CoDeSys 2 and XSOFT-CoDeSys 3 among supported engineering environments for the XV-152 family. Compatibility depends on the project version, installed runtime, and programming tools available for the particular unit.

5. Can I hot-swap this HMI while the machine is running?

Do not assume live replacement is supported. The panel requires a 24 VDC supply and connects to machine-control and communication circuits. Follow the machine manufacturer’s shutdown and isolation procedures, and ensure the process is in a safe state before disconnecting it.

6. Is the Eaton XV-152-D6-10TVRC-10 still manufactured?

Eaton lists catalog number 150611, model XV-152-D6-10TVRC-10, as discontinued. Replacement availability depends on remaining stock and serviceable units. Confirm the exact model code and request condition and test details before purchasing.

7. Will the replacement retain the existing HMI program and settings?

Do not assume that the application will transfer automatically. Back up the visualization project, PLC program, communication settings, and any available retentive data before removing the original panel. Confirm software and runtime compatibility, then test screen operation, PLC communications, alarms, and control commands before returning the machine to service.