Description
Technical Specifications
| Parameter | Specification |
|---|---|
| Model | SAI143-H63 |
| Manufacturer | Yokogawa |
| Module type | Analog current input |
| Number of channels | 16 |
| Channel isolation | Module isolation |
| Rated input range | 4–20 mA DC |
| Permissible input range | 0–25 mA |
| Input accuracy | ±16 μA, over 0.05–23 mA |
| Data update frequency | 40 ms |
| Temperature drift | ±16 μA per 10°C |
| Input impedance, power ON | Approximately 250 Ω plus internal protection-circuit voltage drop |
| Input impedance, power OFF | 500 kΩ minimum |
| Transmitter supply | 16.15 V minimum at 20 mA; 26.4 V maximum at 0 mA |
| Transmitter current limit | 25 mA |
| 2-wire / 4-wire configuration | Individually selectable by setting pins |
| HART communication | Supported |
| Input-to-system withstand voltage | 1.5 kV AC for 1 minute |
| Maximum current consumption | 320 mA at 5 V; 550 mA at 24 V |
| Operating temperature | -20°C to +70°C |
| Interface | Signal cable interface adapter |
| Explosion protection | Not included |
| Weight | Approximately 0.39 kg with signal cable interface adapter |
Product Introduction
Yokogawa SAI143-H63 Analog Input Module
The Yokogawa SAI143-H63 is a 16-channel analog current input module designed for Yokogawa distributed control and safety-system I/O installations. It accepts 4–20 mA signals, provides module-level isolation, and supports HART communication for compatible field transmitters. Its signal cable interface adapter configuration distinguishes it from versions intended for pressure-clamp terminal blocks or MIL cable connections.

SAI143-H63
The module’s 40 ms data update frequency and ±16 μA rated accuracy support process-variable acquisition in applications requiring consistent signal monitoring. Individual 2-wire and 4-wire channel settings allow different transmitter arrangements, but the field wiring and transmitter power requirements must be checked before installation.
Application Scenarios & Field Pitfalls
The SAI143-H63 is suitable for process installations that collect analog measurements from pressure, flow, level, and other 4–20 mA transmitters. HART support adds access to compatible instrument information through the control-system communication architecture, subject to system software and configuration requirements.
Typical application scenarios
- Pressure measurement: Acquires 4–20 mA signals from pressure transmitters and supports HART-enabled instrument maintenance.
- Flow monitoring: Collects flow-transmitter signals for process monitoring and control.
- Tank and vessel level measurement: Receives analog output from compatible level transmitters.
- Safety-system signal acquisition: Supports analog input applications in compatible Yokogawa ProSafe-RS configurations.
Field engineering warnings
- Check the complete suffix. The SAI143-H63 is not identical to SAI143-S63. The H version supports HART, while the S version is the standard type. The
6and3suffixes also determine the connection arrangement and environmental specification. - Verify the cable adapter. This version uses a signal cable interface adapter. Confirm the corresponding cable, terminal arrangement, and cabinet connection before ordering. Do not assume that a pressure-clamp or MIL-cable installation can accept it directly.
- Check transmitter wiring. The module supports individually selected 2-wire and 4-wire configurations. Incorrect setting-pin positions can prevent proper signal acquisition or create wiring problems.
- Observe intrinsic-safety restrictions. The published specification states that Zener barriers must not be connected to this module. Confirm the approved isolation-barrier arrangement for hazardous-area circuits.
- Confirm software compatibility. HART functionality requires the applicable Yokogawa system software support. The HART suffix is associated with release R1.02.00 or later; check the actual host-system version before replacement.
Related Products
| Model | Function and difference |
|---|---|
| SAI143-S63 | Standard 16-channel 4–20 mA analog input version without the HART option. |
| SAI143-H53 | HART analog input variant with a different external connection configuration; verify the required cable or terminal arrangement. |
| SAI143-H63/PRP | configuration with a prevention pin for incorrect insertion, where specified. |
| SAV144 | Isolated analog voltage input module for 1–10 V signals; not a current-input substitute. |
| SAT145 | Isolated thermocouple/mV input module for temperature measurement. |
| SAR145 | Isolated RTD input module for resistance temperature sensors. |
| SAI533 | Isolated analog current output module; used for output signals rather than field-current acquisition. |
Procurement recommendation: Specify the complete model , including the HART option and signal cable interface adapter. Before installation, compare the nameplate, adapter type, setting-pin configuration, and host-system software revision with the existing module. The SAI143 family supports dual-redundant configurations, but the terminal assembly and system arrangement must also support the intended redundancy design.