Schneider AS-S908-120 | Remote I/O Processor | Dual-Coaxial Cable Interface

  • Full requested designation: AS-S908-120RP
  • Base hardware model: AS-S908-120
  • Manufacturer: Modicon / Schneider Electric
  • System: Modicon 984 PLC
  • Network: S908 Remote I/O
  • Product type: Slot-mounted remote I/O processor
  • Cable configuration: Dual coaxial cable
  • Primary purpose: Maintains communication between a compatible 984 controller and distributed 800-Series I/O drops.
Category: SKU: Schneider AS-S908-120

Description

Key Technical Specifications

Parameter Specification
Communication network Modicon S908 Remote I/O
Communication rate 1.544 Mbit/s
Communication method Biphase-level modulation
Message format HDLC
Coaxial connections 2 F-type coaxial connectors
Cable arrangement Dual-cable / redundant path
Power supply +5 VDC
Current consumption 1,500 mA at +5 VDC
Operating temperature 0 to +60°C
Relative humidity 0–95%, non-condensing
Shock resistance 10 G, 11 ms
Mounting One option slot in H8xx-209 housing
Weight Approximately 1.2 kg

 

Product Introduction

The Modicon AS-S908-120RP is identified by its base model as a dual-cable S908 Remote I/O processor for legacy Modicon 984 PLC systems. It provides the communication interface between the supervisory controller and remote I/O drops, allowing field signals to be exchanged with the central control system over the S908 network.

The dual-cable arrangement is intended for systems requiring an alternate communication path. The processor uses two coaxial connections and operates at 1.544 Mbit/s using biphase-level modulation and HDLC message formatting. It is a specialized legacy communication component; it should not be confused with Ethernet-based remote I/O equipment or newer Modicon communication modules.

AS-S908-120RP

Application Scenarios & Field Pitfalls

Typical applications

  • Modicon 984-685 and 984-785 PLC remote I/O networks.
  • Distributed 800-Series I/O installations.
  • Dual-cable S908 communication architectures.
  • Legacy process control systems requiring maintenance or replacement of an existing remote I/O processor.

Important engineering checks

  1. Controller compatibility: The technical manual identifies AS-S908-120 as a slot-mounted processor for compatible 984-685/785 controllers. Do not assume compatibility with every 984 model.
  2. Executive cartridge: The documented configuration requires the AS-E908-131 Executive Cartridge. Confirm the installed cartridge and supported drop configuration.
  3. Cable topology: Both coaxial paths, connectors, cable condition, and network termination must be checked. A dual-cable processor does not by itself guarantee a functioning redundant network.
  4. Power supply: Verify the +5 VDC backplane supply can support the processor’s 1.5 A demand.
  5. Network configuration: Confirm the number of remote drops and the installed I/O architecture before replacing the processor.

 

Related Products

Model Function Relationship
AS–110 Single-cable remote I/O processor Single-cable counterpart
AS-E908-131 Executive Cartridge Required configuration component
AS-E908-016 Executive Cartridge Alternative drop-capacity configuration
AS-S911-800 984 Hot Standby module Separate standby function, not a replacement

The AS–110 is not a direct substitute when the installed system requires dual-cable communication.

 

Procurement and Quality Control

The AS–120 is a discontinued legacy component, so procurement should focus on exact model identification and functional condition rather than appearance alone.

Before accepting an AS–120RP, request:

  • Front and rear photographs showing the complete part number.
  • Confirmation of whether RP is printed on the original OEM label.
  • Connector inspection for damage, corrosion, or looseness.
  • Verification of the +5 VDC power requirement.
  • A functional communication test with a compatible 984/ system, if available.
  • Test documentation identifying the test setup and actual results.

Replacement recommendation: Match the original AS–120 hardware and confirm the installed executive cartridge and dual-cable network arrangement before installation. A generic power-on test is not sufficient to establish remote I/O communication reliability.