Honeywell FC-TSRO-0824 | 8-Channel SIL 3 Relay Output FTA | Safety System Interface

  • Model: FC-TSRO-0824
  • Brand: Honeywell
  • Series: Safety Manager / Honeywell safety-system FTA family
  • Core Function: Interfaces eight relay-based digital outputs with external field wiring.
  • Type: Conformal-coated digital output relay Field Termination Assembly
  • Key Specs: 8 relay output channels; 24 VDC nominal input; 5 A fused maximum output current per channel; up to 250 VAC or 250 VDC switching voltage; SIL 3 application capability.
Category: SKU: Honeywell FC-TSRO-0824

Description

Technical Specifications

Parameter Specification
Product Model FC-TSRO-0824
Manufacturer Honeywell
Product Type Digital output relay FTA
Assembly Variant Conformal-coated
Number of Output Channels 8
Nominal Input Voltage 24 VDC
Maximum Input Voltage 36 VDC
Relay Pickup Voltage 19.2 VDC
Typical Input Current 40 mA at 24 VDC
Maximum Output Current 5 A, fused
Minimum Output Current 1 mA at 5 V
Maximum Output Voltage 250 VAC / 250 VDC
Maximum Switched Load 1,250 VA / 150 W, subject to load conditions
Fuse Rating 5 A
Fuse Size 5 × 20 mm
Fuse Manufacturer / Part Schurter 0001.2511
Safety Capability Up to and including SIL 3, subject to approved system configuration
Approvals CE, UL, TÜV, CSA
Dimensions 300 × 70 × 60 mm
Mounting TS32 / TS35 × 7.5 DIN rail
Maximum Wire Size 2.5 mm² / AWG 14
Operating Temperature -5°C to +60°C

Specifications are taken from Honeywell TSRO-0824 hardware documentation. The listed electrical ratings are family-level specifications; confirm the exact FC revision, load type, and installation conditions before applying them to a replacement.

 

Product Introduction

Honeywell FC-TSRO-0824 Relay Output Field Termination Assembly

The Honeywell FC-TSRO-0824 is an eight-channel relay output termination assembly designed for safety-system field interfaces. It connects the system interconnection cable to external wiring and provides relay contacts for switching field loads. Its conformal-coated construction distinguishes it from the standard FS-TSRO-0824 version.

FC-TSRO-0824

For maintenance teams, the key considerations are relay contact ratings, individual channel fusing, field-load characteristics, and compatibility with the installed safety-system architecture. It is a termination assembly, not a standalone safety controller or general-purpose PLC output card.

 

Application Scenarios & Field Pitfalls

The FC-TSRO-0824 is used where safety-system output signals must operate external equipment through relay contacts. Typical field problems include incorrect load selection, blown channel fuses, mismatched termination hardware, and replacement with an output assembly that has a different electrical interface. These errors can interrupt critical shutdown or equipment-control functions.

Typical applications

  • Safety shutdown circuits: Relay switching for compatible safety-system output functions.
  • Industrial equipment interlocking: Interfaces safety-system commands with external electrical circuits.
  • Process isolation systems: Supports relay-based control of compatible actuators and auxiliary equipment.
  • Harsh industrial installations: The conformal-coated FC version is intended for environments where additional board-level protection is required.

Engineering checks before installation

  1. Confirm the exact assembly variant. FC- is the conformal-coated version. Do not substitute FS- without checking the environmental and hardware requirements.
  2. Verify relay load ratings. The 5 A rating is not a universal rating for every load. Check AC versus DC switching, inrush current, inductive-load suppression, and the specified load curve.
  3. Inspect channel fuses. Confirm fuse rating and type before replacement. Do not install a higher-rated fuse to overcome repeated fuse failures.
  4. Check system and cable compatibility. Verify the system interconnection cable, termination arrangement, and safety-system configuration against the installed hardware.
  5. Do not assume SIL 3 from the part number alone. The family is documented for applications up to SIL 3, but the achieved safety integrity depends on the complete approved architecture, diagnostics, application design, and validation.
  6. Check the connected field circuit before energizing. Confirm terminal assignments, external supply voltage, grounding, and isolation requirements.

Honeywell documentation identifies the eight-channel relay FTA and its SIL 3 application capability. The conformal-coated FC variant is separately identified in the product and certification records.

 

Related Products

The following Honeywell assemblies have related safety-system termination functions. They are comparison references, not guaranteed direct replacements.

Model Function Difference Potential Use
FS- Standard, non-FC version of the eight-channel relay FTA Applications not requiring the FC conformal-coated variant
FC-TSRO-08UNI Eight-channel relay output FTA with common power arrangement Applications designed for the common-power configuration
FC-TRO-0824 Eight-channel relay-contact digital output termination assembly Compatible relay output applications requiring a different FTA design
FC-TSDO-0824 Eight-channel 24 VDC fail-safe digital output FTA, not a relay-contact equivalent Solid-state safety output applications
FC-TSDO-0824C Current-limited 24 VDC digital output FTA Applications requiring current-limited solid-state outputs
FC-TSDI-1624C Sixteen-channel current-limited digital input FTA Safety-system input signal termination
FC-TSDI-16UNI Sixteen-channel universal fail-safe digital input FTA Compatible universal digital input applications

Honeywell’s FTA model listings distinguish relay outputs from solid-state fail-safe outputs and digital inputs. Selection must follow the original I/O design rather than channel count alone.

Procurement note: When requesting the FC-, specify the complete part number and confirm the conformal-coated version. Ask for photographs of the product label, terminal side, and revision markings. For safety-related service, also verify hardware revision, certification documentation, storage history, and functional test records before installation.