SC-UCMX01 Honeywell 28-Channel Mixed I/O Process Controller

  • Manufacturer: Honeywell
  • Product Model: SC-UCMX01
  • Part Number: 51307195-175 (supplier-associated; exact OEM mapping not confirmed)
  • Product Family: ControlEdge RTU
  • Product Type: Non-redundant process controller with onboard mixed I/O
  • I/O Capacity: 28 channels
  • Primary Function: Remote process control, data acquisition, and SCADA communication
  • Programming Environment: ControlEdge Builder
  • Programming Standard: IEC 61131-3
Category: SKU: SC-UCMX01 28-Channel

Description

Key Technical Specifications

Parameter Specification
Controller type Non-redundant RTU controller
Processor Dual-core ARM Cortex-A9, 667 MHz
RAM 128 MB
Program flash 32 MB
Nonvolatile memory 4 Mbits
Supply voltage 24 VDC nominal
Operating voltage range 18–30 VDC
Maximum rated input current 1.20 A at 30 VDC, controller plus 9 IOMs
Onboard I/O 28 channels
Analog inputs 8, 4–20 mA or 1–5 VDC, 16-bit
Analog outputs 2, 4–20 mA, 12-bit
Digital inputs 10, 24 VDC
Digital outputs 6, 24 VDC, 80 mA/channel maximum
Pulse inputs 2, configurable as pulse or digital inputs
Ethernet 2 × 10/100Base-TX
Serial interfaces 2 × RS-232 and 2 × RS-485
Supported protocols Modbus TCP/RTU, DNP3, Enron Modbus, HART-IP
Mounting DIN rail, TH35-7.5
Dimensions 190 × 99 × 141 mm
Weight Approximately 700 g
Operating temperature -40 to +75°C
Storage temperature -40 to +85°C
Relative humidity 5–95%, non-condensing

 

Product Introduction

The Honeywell SC-UCMX01 ControlEdge RTU is a compact, non-redundant process controller designed for remote automation installations. Its integrated 28-channel mixed I/O arrangement combines analog inputs, analog outputs, digital inputs, digital outputs, and high-speed pulse inputs in one controller assembly. This reduces the need for separate I/O hardware in smaller remote control stations while retaining expansion capability.

SC-UCMX01 51307195-175

The controller uses a dual-core ARM Cortex-A9 processor and supports IEC 61131-3 programming through Honeywell ControlEdge Builder. Its Ethernet and serial interfaces allow communication with SCADA systems, field instruments, and local equipment. Supported protocols include Modbus, DNP3, Enron Modbus, and HART-IP. Typical applications include remote pumping stations, pipeline monitoring, gas metering, utility installations, and distributed process control.

 

Application Scenarios and Field Pitfalls

Typical applications

  • Oil and gas pipeline monitoring and remote control.
  • Gas metering and electronic flow measurement.
  • Water and wastewater treatment facilities.
  • Remote pumping and compressor stations.
  • Utility substations and distributed process installations.
  • HART-enabled field instrumentation networks.

Important engineering considerations

  1. Power supply: The controller requires 18–30 VDC. Do not substitute an AC-powered controller based on misleading catalog specifications.
  2. I/O configuration: The onboard 28-channel arrangement has a defined channel mix. Verify field wiring against the actual I/O terminal assignments.
  3. Signal isolation: The documented analog and digital onboard channels are not universally isolated. Check grounding and signal common arrangements before connecting field devices.
  4. Communications: Confirm Ethernet addressing, serial port configuration, protocol settings, and SCADA register mapping.
  5. Expansion: The documented architecture supports up to nine expansion I/O modules. Expansion layout and end-plate requirements must be checked.
  6. Firmware and project compatibility: Match the controller firmware release with the ControlEdge Builder project and existing RTU configuration.

 

Related Products and Variants

Model Description
SC-UCNN11 Redundant ControlEdge RTU controller
SC-UMIX01 28-channel mixed I/O module
SC-TEPR01 Right expansion end plate
SC-TEPL01 Left expansion end plate
SC-PCMX01 Processor module designation appearing in secondary catalog records; verify separately

SC-UCMX01 and SC-PCMX01 should not be treated as equivalent part numbers. Honeywell’s published hardware documentation describes SC-UCMX01 as a complete CPM-and-IOTA controller assembly.

 

Procurement and Quality Control

The main procurement issue is the relationship between SC-UCMX01 and 51307195-175. Supplier catalogs associate these identifiers, but Honeywell’s retrieved technical specification confirms the SC-UCMX01 model without establishing that exact numeric part-number mapping.

Before purchasing, verify:

  • Complete product label and Honeywell part number.
  • Whether the item is the complete SC-UCMX01 assembly or an individual CPM.
  • Included IOTA and onboard I/O hardware.
  • Hardware revision and firmware release.
  • Terminal condition and connector integrity.
  • Power-on diagnostics and communication test results.
  • Availability of the existing ControlEdge Builder project and configuration backup.

Replacement recommendation: Use SC- as the primary identification, but confirm 51307195-175 against the original nameplate before ordering. A similar-looking processor module alone may not provide the complete controller assembly required by the installation.