TC-303-01-2M0 Trusted TMR Remote Expander Cable Assembly

  • Model: TC-303-01-2M0
  • Brand: ICS TRIPLEX / Rockwell Automation
  • Series: Trusted TMR
  • Core Function: Remote expansion communications connection between the T8314 Fibre TX/RX Unit and T8310 Trusted Expander Processor
  • Type: Trusted communications cable assembly
  • Key Specifications: TC-303-01 cable type; 96-way Type C connector; three 4-way LEMO plugs; individually screened Cat 5 cable; PVC sheath; 250 Mbit/s Trusted remote expansion interface
Category: SKU: TC-303-01-2M0

Description

ICS TRIPLEX TC-303-01-2M0 Trusted Remote Expansion Cable

Key Technical Specifications

Parameter Specification
Manufacturer ICS TRIPLEX
Part Number TC-303-01-2M0
Product Family Trusted
Product Type Communications / Remote Expansion Cable
Cable Type TC-303-01
System Architecture Trusted TMR
Primary Connection T8314 Fibre TX/RX Unit → T8310 Expander Processor
T8310 End 96-way Type C connector
Connector Housing Double-width hood
T8314 End Three 4-way LEMO plugs
Cable Category Cat 5
Screening Individually screened
Sheath PVC
Application Remote Trusted Expander connection
Nominal Link Rate 250 Mbit/s
Length Code 2M0 configuration

The documented TC-303-01 construction uses individually screened Cat 5 cable with a PVC sheath. The T8310 end uses a 96-way Type C connector in a double-width hood, while the T8314 end uses three 4-way LEMO plugs.

 

Product Introduction

The ICS TRIPLEX TC-303-01-2M0 is a cable assembly within the Trusted communications cable family. Its purpose is to carry the Trusted remote expansion connection between a T8314 Fibre TX/RX Unit and a T8310 Expander Processor installed in a remote Trusted Expander Chassis. Rockwell documentation identifies TC-303-01 specifically as the 250 Mbit/s remote expander incoming cable from to .

The TC-303-01 designation is important because the cable is part of the Trusted expansion architecture rather than a general-purpose Ethernet patch cable. The physical termination is also specialized, with the side using a 96-way Type C connector and the side using three 4-way LEMO plugs.

TC-303-02-4M0

Application Scenarios & Field Pitfalls — Engineer’s Perspective

TC-303-01 is used when a Trusted system requires a remote expansion chassis connection through the fibre interface. It belongs between the fibre transceiver hardware and the remote expander processor; it should not be treated as a standard network cable or as an I/O module.

Typical Applications

  • Remote Trusted expansion: Connects the Fibre TX/RX Unit with the Expander Processor.
  • Distributed Trusted I/O: Supports communication with remote Trusted Expander Chassis installations.
  • Safety-system maintenance: Used when the existing TC-303 cable assembly requires replacement.
  • Legacy Trusted system support: Appropriate for maintaining installed Trusted expansion architectures where the original cable specification must be preserved.

Field Pitfalls

Do not substitute a standard Cat 5 cable. Although TC-303-01 uses Cat 5 cable internally, the complete assembly has specialized connectors, screening, hood construction, and Trusted-specific wiring. The cable assembly is therefore not equivalent to an ordinary Ethernet cable.

Do not confuse TC-303-01 with TC-302-01. The Trusted Fibre TX/RX documentation identifies TC-302-01 as the outgoing cable from T8312 to , while TC-303-01 is the incoming cable from to . Their system positions are different.

Check connector condition carefully. The -side 96-way Type C connector and three LEMO connections at the side are integral to the cable assembly. Pin damage, poor shielding continuity, or incorrect mating can create intermittent remote-expansion communication faults that may initially appear to be an expander or fibre-interface problem.

 

Related Products

  • — Trusted Expander Processor; the processor-side endpoint for TC-303-01.
  • — Trusted Fibre TX/RX Unit; the fibre-interface-side endpoint for TC-303-01.
  • T8312 — Trusted Expander Interface Adaptor; associated with the outgoing remote-expansion path.
  • TC-302-01 — Remote expansion cable from T8312 to ; different direction and system position.
  • TC-302-02 — Related remote expansion cable variant; verify construction and termination before substitution.
  • TC-303-02 — Alternative TC-303 cable construction using LSF/OH sheath rather than the PVC construction specified for TC-303-01.
  • TC-301-01 — Local expansion cable from T8312 to .
  • TC-301-02 — Related local expansion cable variant.
  • T8300 — Trusted Expander Chassis that houses Trusted expansion equipment and I/O.

 

Procurement Note

For TC-303-01-2M0, verify the complete part number rather than purchasing by a generic description such as “Trusted communication cable.” The critical checks are the TC-303-01 cable type, 2M0 length designation, / application, 96-way Type C connector, three 4-way LEMO plugs, and cable construction.

A number of commercial listings incorrectly describe TC-303-01-2M0 as an automation controller, digital I/O module, analog output module, or high-voltage inverter. Those descriptions are inconsistent with the Trusted TC300 communications-cable documentation.

For a replacement in an operating Trusted system, I would verify the installed cable label and connector arrangement against the existing / architecture before approving the part.