760-P1-G1-S1-LO-A20-R Feeder Management / Protection Relay

Manufacturer: GE Multilin
Model: 760-P1-G1-S1-LO-A20-R
Product Type: Feeder Management & Protection Relay
Series: Multilin 760
Phase CT: 1 A
Zero-Sequence CT: 1 A
Sensitive Ground: 1 A
Analog Outputs: 8 × 4–20 mA
Control Power: 20–60 VDC / 20–48 VAC
Communication: Modbus RTU / DNP 3.0

Category: SKU: 760-P1-G1-S1-LO-A20-R

Description

GE Multilin 760-P1-G1-S1-LO-A20-R Product Description

Product Overview

GE Multilin 760-P1-G1-S1-LO-A20-R is a 760 Series Feeder Management Relay designed for protection, control, monitoring, metering, and automation of electrical distribution feeders. It is a drawout-type digital protection relay within the GE Multilin 750/760 Feeder Management Relay family.

This specific configuration features 1 A phase-current inputs, 1 A zero-sequence current inputs, 1 A sensitive-ground current input, low-voltage control power, eight 4–20 mA analog outputs, and a red breaker-closed LED. It also supports Modbus RTU and DNP 3.0 communications and provides event recording and waveform-capture functions.

Technical Specifications

Parameter Specification
Manufacturer GE Multilin / General Electric
Model 760-P1-G1-S1-LO-A20-R
Product Type Feeder Management / Protection Relay
Series Multilin 760
Application Feeder protection and distribution management
Phase Current Input 1 A
Zero-Sequence Current Input 1 A
Sensitive Ground Input 1 A
Control Power 20–60 VDC / 20–48 VAC, 48–62 Hz
Analog Outputs 8 × 4–20 mA
Breaker Indication Red LED
Communication Protocols Modbus RTU, DNP 3.0
Display 40-character LCD
Construction Drawout
Data Recording Event and waveform recording
Waveform Sampling 16 samples/cycle
Insulation Voltage 300 V
Overvoltage Category II
Pollution Degree II

The above configuration is specifically documented with 1 A current inputs and eight 4–20 mA outputs.

Main Features and Advantages

Comprehensive Feeder Protection

The 760-P1-G1-S1-LO-A20-R provides protection and control functions for distribution feeders and can also provide backup protection for equipment such as transformers and transmission-line feeders.

1 A Current-Transformer Inputs

This order code uses 1 A phase, zero-sequence and sensitive-ground current inputs, making it suitable for installations using 1 A CT secondaries. The CT rating should be carefully matched when replacing an existing relay.

760-P1-G1-S1-LO-A20-R

Eight 4–20 mA Analog Outputs

The A20 option provides eight 4–20 mA analog outputs, allowing measured or calculated electrical parameters to be transmitted to PLC, DCS, SCADA or other monitoring equipment.

Low-Voltage Control Power

The LO configuration supports 20–60 VDC or 20–48 VAC at 48–62 Hz, making the relay appropriate for control cabinets with low-voltage auxiliary supplies.

Reclosing and Feeder Management

The 760 platform provides feeder management functions including automatic reclosing and protection logic. This can help restore feeder service after transient faults while maintaining protection against persistent faults.

Communication and Data Recording

The relay supports Modbus RTU and DNP 3.0, enabling integration with supervisory control systems. Event records and waveform capture assist with post-fault analysis, commissioning and maintenance.

Drawout Construction

The relay uses a drawout construction, allowing the electronic relay unit to be removed from its case for maintenance or replacement. Note that the SR760 case is normally separate from the relay unit.

Application Fields

Electrical Distribution

The primary application is medium- and low-voltage feeder protection. The relay monitors feeder current and provides protection and control functions for distribution circuits.

Industrial Plants

The relay is suitable for industrial power-distribution systems supplying motors, transformers, pumps, compressors and other process loads.

Power Generation

In generating facilities, the 760 can protect auxiliary distribution feeders and provide backup protection for transformers and related electrical equipment.

Oil & Gas and Petrochemical

Refineries and petrochemical plants can use the relay for feeder protection, breaker monitoring, fault recording and integration with plant SCADA systems.

Infrastructure and Utilities

Water-treatment plants, transportation infrastructure and utility distribution systems can use the 760 for feeder monitoring and automated protection.

Retrofit and Maintenance

The 760-P1-G1-S1-LO-A20-R is especially useful when maintaining existing GE Multilin 760 installations. The complete order code is important because the 760 family contains numerous variants with different CT ratings, power supplies, analog outputs and communication/display options. GE Multilin product listings continue to identify this exact configuration as part of the 750/760 feeder relay family.

Related Products

  • GE Multilin 760-P1-G1-S1-LO-A20-R-T — closely related configuration with enhanced display and Ethernet.
  • GE Multilin 760-P1-G1-S1-LO-A10-R — related 760 configuration with eight 0–10 mA analog outputs.
  • GE Multilin 760-P5-G5-S5-LO-A20-R — related 760 feeder relay with different current-input and control-power configuration.
  • GE Multilin 750-P1-G1-S1-HI-A20-R — related 750 Series feeder-management relay.
  • GE Multilin SR760-CASE — compatible relay case; the case may be supplied separately from the drawout relay.